Circuit Breaker Shunt Trips

A shunt trip is a coil-operated accessory inside a circuit breaker that trips the breaker when its coil is energized, so the breaker can be opened from a remote switch, relay or emergency stop circuit. BRAH Electric lists 23 shunt trips: 21 for General Electric Power Break I insulated case breakers and two for Merlin Gerin Compact CM breakers. Control voltages run from 12VDC to 480/600VAC. Each listing shows the family, type, voltage and the breaker frame size the shunt trip suits.

A part that replaces an OEM part number is listed under that number as well as under its BRAH part number, so the results count below can be higher than the number of parts.

46 Results(Showing 1 - 20)
BRAH BE-CMST120VAC Shunt Trip – replaces Merlin Gerin 55592
BE-CMST120VAC
Substitute for Merlin Gerin 55592
View Product
FamilyCompact CM
TypeCMST
Voltage120VAC
Frame Size Suitable800A - 3200A
Merlin Gerin 55592 replacement Shunt Trip – BRAH BE-CMST120VAC
55592
BRAH BE-CMST120VAC is the direct substitute for Merlin Gerin 55592
View Product
FamilyCompact CM
TypeCMST
Voltage120VAC
Frame Size Suitable800A - 3200A
BRAH BE-CMST24VDC Shunt Trip – replaces Merlin Gerin 55544
BE-CMST24VDC
Substitute for Merlin Gerin 55544
View Product
FamilyCompact CM
TypeCMST
Voltage24VDC
Frame Size Suitable800A - 3200A
Merlin Gerin 55544 replacement Shunt Trip – BRAH BE-CMST24VDC
55544
BRAH BE-CMST24VDC is the direct substitute for Merlin Gerin 55544
View Product
FamilyCompact CM
TypeCMST
Voltage24VDC
Frame Size Suitable800A - 3200A
BRAH Electric factory products

Why BRAH Electric?

We're the industry leader in direct replacement.

Factory New
Drop-in fit
Matches OEM Specs
Ships Worldwide
2-Year Warranty included
BRAH BE-TPST10 Shunt Trip – replaces General Electric TPST10
BE-TPST10
Substitute for General Electric TPST10
View Product
FamilyPower Break I
TypeTPST
Voltage125VDC
Frame Size Suitable800A - 2000A
General Electric TPST10 replacement Shunt Trip – BRAH BE-TPST10
TPST10
BRAH BE-TPST10 is the direct substitute for General Electric TPST10
View Product
FamilyPower Break I
TypeTPST
Voltage125VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST11 Shunt Trip – replaces General Electric TPST11
BE-TPST11
Substitute for General Electric TPST11
View Product
FamilyPower Break I
TypeTPST
Voltage250VDC
Frame Size Suitable800A - 2000A
General Electric TPST11 replacement Shunt Trip – BRAH BE-TPST11
TPST11
BRAH BE-TPST11 is the direct substitute for General Electric TPST11
View Product
FamilyPower Break I
TypeTPST
Voltage250VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST12 Shunt Trip – replaces General Electric TPST12
BE-TPST12
Substitute for General Electric TPST12
View Product
FamilyPower Break I
TypeTPST
Voltage120/240VAC
Frame Size Suitable800A - 2000A
General Electric TPST12 replacement Shunt Trip – BRAH BE-TPST12
TPST12
BRAH BE-TPST12 is the direct substitute for General Electric TPST12
View Product
FamilyPower Break I
TypeTPST
Voltage120/240VAC
Frame Size Suitable800A - 2000A
BRAH BE-TPST13 Shunt Trip – replaces General Electric TPST13
BE-TPST13
Substitute for General Electric TPST13
View Product
FamilyPower Break I
TypeTPST
Voltage480/600VAC
Frame Size Suitable800A - 2000A
General Electric TPST13 replacement Shunt Trip – BRAH BE-TPST13
TPST13
BRAH BE-TPST13 is the direct substitute for General Electric TPST13
View Product
FamilyPower Break I
TypeTPST
Voltage480/600VAC
Frame Size Suitable800A - 2000A
BRAH BE-TPST7 Shunt Trip – replaces General Electric TPST7
BE-TPST7
Substitute for General Electric TPST7
View Product
FamilyPower Break I
TypeTPST
Voltage12VDC
Frame Size Suitable800A - 2000A
General Electric TPST7 replacement Shunt Trip – BRAH BE-TPST7
TPST7
BRAH BE-TPST7 is the direct substitute for General Electric TPST7
View Product
FamilyPower Break I
TypeTPST
Voltage12VDC
Frame Size Suitable800A - 2000A
BRAH Electric support team

Need Assistance?

Our support team is here to assist you with any inquiries or issues. Get in touch for personalized support.

Contact us

BRAH Electric products

30-day returns

Returns accepted within 30 days of shipment with an RMA; a 25–50% restocking charge applies.

Read the return policy
BRAH BE-TPST8 Shunt Trip – replaces General Electric TPST8
BE-TPST8
Substitute for General Electric TPST8
View Product
FamilyPower Break I
TypeTPST
Voltage24VDC
Frame Size Suitable800A - 2000A
General Electric TPST8 replacement Shunt Trip – BRAH BE-TPST8
TPST8
BRAH BE-TPST8 is the direct substitute for General Electric TPST8
View Product
FamilyPower Break I
TypeTPST
Voltage24VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST9 Shunt Trip – replaces General Electric TPSY9
BE-TPST9
Substitute for General Electric TPSY9
View Product
FamilyPower Break I
TypeTPST
Voltage48VDC
Frame Size Suitable800A - 2000A
General Electric TPSY9 replacement Shunt Trip – BRAH BE-TPST9
TPSY9
BRAH BE-TPST9 is the direct substitute for General Electric TPSY9
View Product
FamilyPower Break I
TypeTPST
Voltage48VDC
Frame Size Suitable800A - 2000A
BRAH BE-TSST10L Shunt Trip – replaces General Electric TSST10L
BE-TSST10L
Substitute for General Electric TSST10L
View Product
FamilyPower Break I
TypeTSST
Voltage125VDC
Frame Size Suitable2500A - 4000A
General Electric TSST10L replacement Shunt Trip – BRAH BE-TSST10L
TSST10L
BRAH BE-TSST10L is the direct substitute for General Electric TSST10L
View Product
FamilyPower Break I
TypeTSST
Voltage125VDC
Frame Size Suitable2500A - 4000A

Shunt trips by breaker frame and control voltage

Overview

For Power Break I there are two types. Type TPST fits the small frame breakers (TRLA, TRLL, TRPA, TRPP, TRL and TRP) rated 800A to 2000A. Type TSST fits the large frame breakers (TPS, THS, TPSS and THSS) rated 2500A to 4000A, and is listed in L and R versions, shown by the last letter of the part number; match the letter on the part being replaced. Both types are offered in 12VDC, 24VDC, 48VDC, 125VDC, 250VDC, 120/240VAC and 480/600VAC.

For Merlin Gerin Compact CM frame breakers rated 800A to 3200A, BE-CMST24VDC replaces OEM part number 55544 and BE-CMST120VAC replaces 55592. Each is a shunt trip assembly with its coil.

How do I choose a shunt trip?

To choose, match the breaker family and frame size, then the control voltage, AC or DC, of the circuit that will energize the coil. The General Electric parts keep the OEM number with a BE- prefix, so BE-TSST9R replaces TSST9R. A shunt trip needs voltage applied to trip the breaker; where a breaker has to open on loss of voltage, an undervoltage release is the part to use. Shunt trips carry a 2-year warranty from the date of invoice.

Need help confirming a match? Call (855) 355-2724.