Circuit Breaker Replacement Parts

BRAH Electric supplies aftermarket circuit breaker replacement parts: rating plugs, shunt trips, undervoltage releases and closing coils, along with face plates, lug terminal kits, mounting brackets, operating handles and other repair parts. They are made as direct replacements for parts on General Electric, Siemens, Square D, Merlin Gerin and Cutler-Hammer breakers. Each listing shows the OEM part number it replaces and the breaker family and frame it suits. Parts are factory new and carry a 2-year warranty, and same day shipping is available on most orders.

A part that replaces an OEM part number is listed under that number as well as under its BRAH part number, so the results count below can be higher than the number of parts.

492 Results(Showing 241 - 260)
BRAH BE-TPST11 Shunt Trip – replaces General Electric TPST11
BE-TPST11
Substitute for General Electric TPST11
View Product
FamilyPower Break I
TypeTPST
Voltage250VDC
Frame Size Suitable800A - 2000A
General Electric TPST11 replacement Shunt Trip – BRAH BE-TPST11
TPST11
BRAH BE-TPST11 is the direct substitute for General Electric TPST11
View Product
FamilyPower Break I
TypeTPST
Voltage250VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST12 Shunt Trip – replaces General Electric TPST12
BE-TPST12
Substitute for General Electric TPST12
View Product
FamilyPower Break I
TypeTPST
Voltage120/240VAC
Frame Size Suitable800A - 2000A
General Electric TPST12 replacement Shunt Trip – BRAH BE-TPST12
TPST12
BRAH BE-TPST12 is the direct substitute for General Electric TPST12
View Product
FamilyPower Break I
TypeTPST
Voltage120/240VAC
Frame Size Suitable800A - 2000A
BRAH Electric factory products

Why BRAH Electric?

We're the industry leader in direct replacement.

Factory New
Drop-in fit
Matches OEM Specs
Ships Worldwide
2-Year Warranty included
BRAH BE-TPST13 Shunt Trip – replaces General Electric TPST13
BE-TPST13
Substitute for General Electric TPST13
View Product
FamilyPower Break I
TypeTPST
Voltage480/600VAC
Frame Size Suitable800A - 2000A
General Electric TPST13 replacement Shunt Trip – BRAH BE-TPST13
TPST13
BRAH BE-TPST13 is the direct substitute for General Electric TPST13
View Product
FamilyPower Break I
TypeTPST
Voltage480/600VAC
Frame Size Suitable800A - 2000A
BRAH BE-TPST7 Shunt Trip – replaces General Electric TPST7
BE-TPST7
Substitute for General Electric TPST7
View Product
FamilyPower Break I
TypeTPST
Voltage12VDC
Frame Size Suitable800A - 2000A
General Electric TPST7 replacement Shunt Trip – BRAH BE-TPST7
TPST7
BRAH BE-TPST7 is the direct substitute for General Electric TPST7
View Product
FamilyPower Break I
TypeTPST
Voltage12VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST8 Shunt Trip – replaces General Electric TPST8
BE-TPST8
Substitute for General Electric TPST8
View Product
FamilyPower Break I
TypeTPST
Voltage24VDC
Frame Size Suitable800A - 2000A
General Electric TPST8 replacement Shunt Trip – BRAH BE-TPST8
TPST8
BRAH BE-TPST8 is the direct substitute for General Electric TPST8
View Product
FamilyPower Break I
TypeTPST
Voltage24VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPST9 Shunt Trip – replaces General Electric TPSY9
BE-TPST9
Substitute for General Electric TPSY9
View Product
FamilyPower Break I
TypeTPST
Voltage48VDC
Frame Size Suitable800A - 2000A
General Electric TPSY9 replacement Shunt Trip – BRAH BE-TPST9
TPSY9
BRAH BE-TPST9 is the direct substitute for General Electric TPSY9
View Product
FamilyPower Break I
TypeTPST
Voltage48VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPUV1 Undervoltage Release – replaces General Electric TPUV1
BE-TPUV1
Substitute for General Electric TPUV1
View Product
FamilyPower Break I
TypeTPUV
Voltage120VAC
Frame Size Suitable800A - 2000A
General Electric TPUV1 replacement Undervoltage Release – BRAH BE-TPUV1
TPUV1
BRAH BE-TPUV1 is the direct substitute for General Electric TPUV1
View Product
FamilyPower Break I
TypeTPUV
Voltage120VAC
Frame Size Suitable800A - 2000A
BRAH Electric support team

Need Assistance?

Our support team is here to assist you with any inquiries or issues. Get in touch for personalized support.

Contact us

BRAH Electric products

30-day returns

Returns accepted within 30 days of shipment with an RMA; a 25–50% restocking charge applies.

Read the return policy
BRAH BE-TPUV10 Undervoltage Release – replaces General Electric TPUV10
BE-TPUV10
Substitute for General Electric TPUV10
View Product
FamilyPower Break I
TypeTPUV
Voltage125VDC
Frame Size Suitable800A - 2000A
General Electric TPUV10 replacement Undervoltage Release – BRAH BE-TPUV10
TPUV10
BRAH BE-TPUV10 is the direct substitute for General Electric TPUV10
View Product
FamilyPower Break I
TypeTPUV
Voltage125VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPUV11 Undervoltage Release – replaces General Electric TPUV11
BE-TPUV11
Substitute for General Electric TPUV11
View Product
FamilyPower Break I
TypeTPUV
Voltage250VDC
Frame Size Suitable800A - 2000A
General Electric TPUV11 replacement Undervoltage Release – BRAH BE-TPUV11
TPUV11
BRAH BE-TPUV11 is the direct substitute for General Electric TPUV11
View Product
FamilyPower Break I
TypeTPUV
Voltage250VDC
Frame Size Suitable800A - 2000A
BRAH BE-TPUV2 Undervoltage Release – replaces General Electric TPUV2
BE-TPUV2
Substitute for General Electric TPUV2
View Product
FamilyPower Break I
TypeTPUV
Voltage240VAC
Frame Size Suitable800A - 2000A
General Electric TPUV2 replacement Undervoltage Release – BRAH BE-TPUV2
TPUV2
BRAH BE-TPUV2 is the direct substitute for General Electric TPUV2
View Product
FamilyPower Break I
TypeTPUV
Voltage240VAC
Frame Size Suitable800A - 2000A

Circuit breaker replacement parts by breaker family

Overview

Rating plugs make up most of this category, with replacements for GE Spectra, Power Break and MicroVersaTrip, Square D Micrologic, and Siemens breakers. Each rating plug listing shows its amperage, the frame type it suits and the maximum frame amperage.

Shunt trips, undervoltage releases and closing coils are listed by voltage and by the breaker family and frame they fit, including GE Power Break and Merlin Gerin Compact.

What each part does: a rating plug sets the ampere rating of a breaker that has an electronic trip unit. A shunt trip opens the breaker when its coil is energized, an undervoltage release opens it when control voltage is lost, and a closing coil closes it electrically. Face plates are the front nameplates of General Electric Power Break I breakers and HPC II switches. Lug terminal kits connect the cables, and operating handles, mounting brackets and repair parts such as lug caps and bumper kits cover the mechanical side of the breaker.

How do I choose a replacement circuit breaker part?

Start from the breaker nameplate, which gives the manufacturer, the family, the frame type and the frame ampere rating. For a rating plug you also need the sensor (CT) rating and the trip unit, because a plug is made for one sensor rating and one trip unit family: Spectra RMS, MicroVersaTrip RMS-9, MicroVersaTrip Plus, Siemens SB-EC or TL, or Square D MicroLogic. For shunt trips, undervoltage releases and closing coils the control voltage, AC or DC, is the second value to match. Many BRAH parts keep the OEM number with a BE- prefix, so BE-TPUV8 replaces General Electric TPUV8. If the old part is missing or its number cannot be read, the frame type and frame rating are enough to narrow the listings by family.

To find a part, filter by amperage, voltage or family, or search for the OEM part number on the part you are replacing. All BRAH circuit breaker parts carry a 2-year warranty from the date of invoice.

Need help confirming a match? Call (855) 355-2724.